38
9 Available protection settings
PXR TRIP UNITS FOR POWER DEFENSE MOLDED CASE CIRCUIT BREAKERS MN012007EN June 2018 www.eaton.com
Register number
Register
address (HEX) Objects
Fp
scale
factor
IEEE
float
Fixed
point (FP)
IEEE
float
Fixed
point (FP) Descriptions Units
404877 406413 130C 190C Maximum VBC V 10
404879 406415 130E 190E Minimum VCA V 10
404881 406417 1310 1910 Maximum VCA V 10
404883 406419 1312 1912 Minimum VAN V 10
404885 406421 1314 1914 Maximum VAN V 10
404887 406423 1316 1916 Minimum VBN V 10
404889 406425 1318 1918 Maximum VBN V 10
404891 406427 131A 191A Minimum VCN V 10
404893 406429 131C 191C Maximum VCN V 10
404959 406495 135E 195E INST/SDT/HIGH_INST count 1
404961 406497 1360 1960 LDT/GFT count 1
404963 406499 1362 1962 Operations count 1
404965 406501 1364 1964 Short delay trip count 1
404967 406503 1366 1966 Inst delay trip count 1
404969 406505 1368 1968 High current delay trip count 1
404971 406507 136A 196A Long delay trip count 1
404973 406509 136C 196C Ground fault trip count 1
404975 406511 136E 196E Total trip count 1
404977 406513 1370 1970 Test trip count 1
404979 406515 1372 1972 Open by comm count 1
404981 406517 1374 1974 Manual open count 1
404983 406519 1376 1976 Time of last operation (Y,M,D,H,M,S) 1
404995 406531 1382 1982 Max device temperature C 1
404997 406533 1384 1984 Time of max device temperature 1
405009 406545 1390 1990 Running time: minute 1
405011 406547 1392 1992 Running time: hour 1
405013 406549 1394 1994 Running time: day 1
405015 406551 1396 1996 Life point 1
Energy objects can be obtained in two-register fixed point data format and four-register encoded format, not supporting
in floating point data format.
The two-register format is presented in units of kilowatt hours. The four registers encoded
energy object occupies register 3 through register 0. Register 3 is the high order register
and register 0 is the low order register. Register 3 high byte contains value corresponding
to engineering units(power of 10 signed exponent). Register 3 low byte contains a mantissa
multiplier value(power of 2 exponent). Register 3 through register 0 contains a 48-bit energy
mantissa in units of watthours. The data format of four registers is shown.