44
9 Available protection settings
PXR TRIP UNITS FOR POWER DEFENSE MOLDED CASE CIRCUIT BREAKERS MN012007EN June 2018 www.eaton.com
Register
Bit
field
Mask
field Set points name R/W Format Value definition
403008 INCOM CAM baud rate R 1 <--> 9600bps see IL01301033e
P8 "for series NRX INCOM
communication adapter module,
baud rate is fixed at 9600 baud and
represented by a value of 01"
403009 Ethernet CAM DHCP enable R 0 <--> false
1 <--> true
403010 Ethernet CAM IP addr. MSB R 0~255 <--> 0~255
403011 Ethernet CAM IP addr. LSB R 0~255 <--> 0~255
403012 Ethernet CAM IP addr. MSB R 0~255 <--> 0~255
403013 Ethernet CAM IP addr. LSB R 0~255 <--> 0~255
403014 Ethernet CAM subnet mask R 16~32 <--> 16~32
403015 Ethernet CAM default gateway R 0~255 <--> 0~255
403016 Ethernet CAM default gateway R 0~255 <--> 0~255
403017 Ethernet CAM reset pin R 0~255 <--> 0~255
403018 Profibus CAM address R 1~125 <--> 1~125
Set points group 4: I/O module group
Register
Bit
field
Mask
field Set points name R/W Format Value definition
403000 15-0 0xFFFF Password W Encoded Default0000”
403001 15-0 0xFFFF I/O module cfg R/W Encoded 0x04FF
403002 15-0 Validity flags 0….15 R/W Encoded For each bit:
0 : corresponding parameter inactive
1 : corresponding parameter active
e.g. Bit 8 = 1
==> parameter 8 = active
403003 15-0 Validity flags 16….31 R/W Encoded For each bit:
0 : corresponding parameter inactive
1 : corresponding parameter active
e.g. Bit 8 = 1
==> parameter 8 = active
403004 15-0 0: digital output 0 R/W Encoded
403005 15-0 1: digital output 1 R/W Encoded
403006 2: digital output 2 R/W Encoded
403007 3: digital output 3 R/W Encoded
403008 4: S0 channel 0 type R/W 0: output disabled
1: sends pulses based on active energy
2: sends pulses based on reactive energy
3: sends pulses based on apparent energy
403009 5: S0 channel 0 scale R/W 0: sends a pulse every
1: W 1: sends a pulse every 10 W
2: sends a pulse every 100 W
3: sends a pulse every 1000 W
403010 6: S0 channel 0 pulse R/W pulse duration x *10 ms
range: 1…50 ==> 10…500 ms
403011 7: S0 channel 1 type R/W 0: output disabled
1: sends pulses based on active energy
2: sends pulses based on reactive energy
3: sends pulses based on apparent energy
403012 8: S0 channel 1 scale R/W 0: sends a pulse every
1 W 1: sends a pulse every 10 W
2: sends a pulse every 100 W
3: sends a pulse every 1000 W
403013 9: S0 channel 1 pulse R/W Pulse duration x *10 ms
Range: 1…50 ==> 10…500 ms
403014 10: Modbus address R/W Modbus ID (= device address)
permitted range: 1…255