9 Available protection settings
PXR TRIP UNITS FOR POWER DEFENSE MOLDED CASE CIRCUIT BREAKERS MN012007EN June 2018 www.eaton.com
Primary status /secondary status/cause code definitions
Definition Code
Open 0x01
Closed 0x02
Tripped 0x03
Alarmed 0x04
Picked-up 0x0D
Definition Code
Not applicable 0x01
Test mode 0x03
Powered-up since last trip/alarm reset 0x07
Alarm 0x08
Definition Code Definition Code
Unknown 0x0000 Fixed hardware instantaneous 0x004C
Normal 0x0001 Set points error 0x004D
Instantaneous 0x0003 Over temperature 0x004E
Aux-power under power 0x000E Long delay neutral over current 0x0050
Current un-balance 0x0011 Ground fault 0x0054
Operations count 0x001F Earth fault 0x0055
Control via communication 0x0021 Calibration 0x0071
Coil supervision 0x0025 Real time clock 0x0088
Battery low voltage alarm 0x0029 MM mode 0x0099
Diagnostics warning #2
(configuration reading failure)
0x002B Breaker mechanism fault 0x009A
Long delay 0x003D Digital bypass 0x07FC
Short delay 0x003E NV memory failure 0x07FD
Phase currents near pickup,
high load alarm
0x0049 Watchdog fault 0x07FE
Making current release 0x004B Motor alarm or trip 0x07FF