48
Step 5 - Standard application
POWERXL DM1 SERIES ADJUSTABLE FREQUENCY DRIVES PUB53696—August 2020   www.eaton.com
Table 17.  Setpoint (Cont.).
P7.2.1 - Standard.
P7.2.1.1
b
PI keypad setpoint 1
ID 1307
Minimum value:
PID1_ProcessUnitMin
Maximum value:
PID1_ProcessUnitMax
Default value:
0.00 varies
Description:
Keypad PI reference value set point 1.
P7.2.1. 3
b
PI wake-up action
ID 2466
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Wake-up when below wake-up level. 
1 = Wake-up when above wake-up-level. 
2 = Wake-up when below wake-up level % from PI setpoint.  
3 = Wake-up when above wake-up level %from PI setpoint.
Description:
This parameter defines the wake-up function action.
P7.2.2 - Setpoint 1.
P7.2.2.1
a
PI setpoint 1 source
ID 1312
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
1
Options:
0 = Not used;
1 = PI keypad setpoint 1;
2 = PI keypad setpoint 2;
3 = AI;
4 = Drive reference pot;
5 = FB process data input 1;
6 = FB process data input 2;
7 = FB process data input 3;
8 = FB process data input 4;
9 = FB process data input 5;
10 = FB process data input 6;
11 = FB process data input 7;
12 = FB process data input 8;
13 = FB PI setpoint 1; or
14 = FB PI setpoint 2.
Description:
Defines source of the setpoint value the drive uses.  This can either be an internal preset value, keypad setpoint, analog signal, or 
fieldbus message.
P7.2.2.2
a
PI setpoint 1 sleep enable
ID 1315
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Disabled; or
1 = Enabled.
Description:
This function will disable the output when the frequency drops below the sleep frequency for the sleep delay time.  The output 
re-engages when feedback rises above the wake-up level.
P7.2.2.3
b
PI setpoint 1 sleep delay
ID 1317
Minimum value:
0.00 s
Maximum value:
3,000.00 s
Default value:
0.00 s
Description:
This parameter sets the delay time after the setpoint drops below the sleep level for this amount of time and then the drives output will 
shut off till the wake up level is met.  It is to prevent large fluctuations when going into the sleep function to save motor run time.
P7.2.2.4
b
PI setpoint 1 wake-up level
ID 1318
Minimum value:
-99999.99 varies
Maximum value:
99999.99 varies
Default value:
0.00 varies
Description:
Defines the level for the PI feedback value to go above top enable the PI output to be re enabled.  This value is based of the % of 
feedback which can be scaled based off the PI unit min./max, values.
P7.2.2.5
b
PI setpoint 1 boost
ID 1320
Minimum value:
-2.00 varies
Maximum value:
2.00 varies
Default value:
1.00 varies
Description:
The setpoint can be boosted via a multiplier value.
.