Step 5 - Standard application
POWERXL DM1 SERIES ADJUSTABLE FREQUENCY DRIVES PUB53696—August 2020 www.eaton.com
Table 20. Ethernet communication (Cont.).
P12.2 - Trusted IP filter (DM1 PRO only).
P12.2.1
Trusted IP white list
ID 68
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
192.168.1.255 0.0.0. 0
0.0.0.0
Description:
Defines the IP addresses in the white list. A setting of 192.168.1.255 enables all connections on the local subnet.
P12.2.2
Trusted IP filter enable
ID 76
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
1
Options:
0 = Disabled; or
1 = Enabled.
Description:
Enables IP white listing. Devices not in the white list will not be able to establish communications with the drive.
P12.3 - Modbus TCP (DM1 PRO only).
P12.3.1
a
Modbus TCP enable
ID 1942
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Disable; or
1 = Enable.
Description:
Enables modbus TCP communications, must be enabled to connect to Power Xpert inControl.
P12.3.2
Modbus TCP connection limit
ID 609
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
5
Description:
Maximum number of connections allowed to the drive.
P12.3.3
Modbus TCP unit identifier number
ID 610
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
1
Description:
Unit identifier unit value for modbus TCP.
P12.3.4
Modbus TCP protocol status
ID 612
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Options:
0 = Stopped;
1 = Operational; or
2 = Faulted.
Description:
This parameter shows the protocol status for modbus TCP communication.
P12.3.5
Modbus TCP fault response
ID 2517
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Only in fieldbus control mode - when fieldbus is the control place and fieldbus fault is active, the drive will fault on loss of
communications. If not in fieldbus control, place will not fault.
1 = In all control modes - no matter the control place setting, if communication is lost, fieldbus fault response will occur.
Description:
Defines the fieldbus fault condition for modbus TCP communication.
P12.4 - Ethernet IP (DM1 PRO only).
P12.4.1
a
Ethernet based protocol select
ID 1997
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Disabled; or
2 = BACnet IP.
Description:
Selects the active communication protocol on the ethernet I/P port.
P12.4.2
Ethernet IP protocol status
ID 608
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Options:
0 = Off;
1 = Operational; or
2 = Faulted.
Description:
Indicates if ethernet protocol is active or not.