37
LCD touchscreen display programming
PRC-E Series Instruction Manual MN014003EN August 2015 www.eaton.com
“From” is the start time of the schedule, start of the
commanded action.
“Until” is the end time of the schedule, end of the
commanded action.
ote:N In the “Schedules” screen, the “From” and “Until”
times are displayed in the military format. When
entering the time schedules in the “Edit Schedule
screen, the times are entered in the standard format
(am/pm).
In the “Schedules” screen, tap on the line of the schedule
that needs to managed.
This will display the “Edit Schedule” screen.
Action of the schedule
The Action” is the command that is sent at the “From”
(start time) of the schedule and reversed at the “Until”, (end
time) of the schedule. The Action” command is formatted
using the name or address of the point in the controller
and the command separated by single space character,
for example GRPA ON or 1F ON, B101 OFF or 1:1B OFF.
There can be multiple commands in the Action” field, but
they must be separated by the single space character for
example “GRPD ON B127 ON”.
ote:N When in the Associate Schedule with Group”
configuration area, the only command allowed is
<the selected group> <ON> which is automatically
entered in the Action” field, and can not be changed.
The general “Schedules” configuration area allows
combination entry of the multiple commands.
Once in the “Edit Schedule” screen, tap the “Action” line.
This will display the alphanumeric keyboard.
Tap character/number buttons to input the name or address
of the point to control, tap the space bar and then input
the command, for example, “GRPH OFF”, “B101 ON,” or
“1:27B ON”.
To find the name or address of the point you can look in the
following screens.
Circuit breaker points; The controllable circuit breaker
address is made up of the panelboard #: the controllable
circuit breaker position in the panelboard. For example,
“3:12B” is the #12 circuit breaker in the #3 panelboard).
From the “Main Menu” screen, tap “Breakers”—tap
on panelboard—tap the number of the circuit breaker of
interest.
The controllable circuit breaker address is located at the
top of the screen, for example, “1:1B”; the name is the
4-character text in the name textbox, for example, “B101”.