69
Web page programming
PRC-E Series Instruction Manual MN014003EN August 2015 www.eaton.com
Editing or creating a new control
Double-click the line of the control.
This opens the “Edit Control” Web page.
Click the radio button of the type of input.
Click the “Input” textbox to open the dropdown list of
digital and universal inputs.
Scroll through and click to choose the two-wire input
connected to the controller.
Setting a time delay
The “Time Delay” is a time value set for the group when
the switch is activated. After the timer delay expires, the
group will be commanded OFF”. For example, if the time
delay is set for 10 minutes, when the input is closed the
group will turn ON”, then, when the time delay reaches
0 the group will turn OFF”.
ote:N For “Maintained” type switches, it does not matter
that the switch remains closed; the group will turn
OFF” after the time delay expires.
To set a time delay, click the hours textbox.
This opens the box for editing.
Input the number of hours for the time delay.
Click the “Minutes” textbox.
This opens the box for editing.
Input the number of minutes for the time delay.