29
Instruction Book IB182923EN September 2018 www.eaton.com
AMH-4.76-VR
+
VR-Series
+
Replacement Circuit Breaker
Figure 6.10. Move the Sharpie
®
15
o
Left and Right
Figure 6.11. Top view of Cam and Marker Interface
Cam
Marker
CloSure Tool
TM
15
O
15
O
Figure 6.13. Determining the Distance Traveled
Figure 6.14. Illustrative Testing Tape Sample
Figure 6.12. Evaluate the CloSure™ Performance
Date, # of Breaker Operations, CloSure Distance
"X" Inches
CloSure Distance
TM
TM
*Note: Use the center of
the marker diameter to
determine "X" distance
If “X” is
>
0.6”, then
the performance is
satisfactory.
*Figure not to scale
8.0 to 10
Inches
5 3/16" Approx