31
Instruction Book IB182923EN September 2018 www.eaton.com
AMH-4.76-VR
+
VR-Series
+
Replacement Circuit Breaker
Table 6.3. Troubleshooting Chart
SYMPTOM INSPECTION AREA PROBABLE DEFECTS
FAILS TO CLOSE
Closing Springs Not Charged Control Circuit
Control Power (Fuse blown or switch off)
Secondary Disconnect Contacts
Motor Cut-off Switch (Poor or burned contacts. Lever not operational.)
Terminals And Connectors (Poor or burned contacts)
Motor (Brushes worn or commutator segment open)
Mechanism
Pawls (Slipping or broken)
Ratchet Wheel (Teeth worn or broken)
Cam Shaft Assembly (Sluggish or jammed)
Oscillator (Reset Spring off or broken)
Closing Springs Not Charged
Circuit Breaker Does Not Close
Control Circuit
(Close Coil does not pick up)
Control Power (Fuse blown or switch off)
Secondary Disconnect Contacts
Anti Pump Relay (Y Relay N.C. contact open or burned or relay picks up)
Close Coil (Open or burned)
Latch Check Switch (Contact open - Bad switch or trip bar not reset)
Auxiliary Switch (B Contact open or burned)
Motor Cut-Off (Contacts open or burned)
Trip Coil Assembly (Clapper fails to reset)
Closing sound but no close
Pole Shaft (Not open fully)
Trip Latch Reset Spring (Damaged or missing)
Trip Bar-D Shaft (Fail to remain reset)
Trip Latch-Hatchet (Fails to remain reset)
Trip Floor Tripper (Fails to remain reset)
Close Latch (Binding)
Close Latch Roller (Binding)
Trip Circuit Energized
UNDESIRABLY CLOSES
Control Circuit
Close Circuit (CS/C getting shorted)
Mechanism
Close Release Latch (Fails to reset)
Close Floor Tripper (Fails to reset)
FAILS TO CLOSE
No Trip Sound Control Circuit Control Power (Fuse blown or switch off)
Secondary Disconnect Contacts
Auxiliary Switch (A contact not making poor or burned)
Trip Coil (Burned or open)
Terminals and connections (Poor or burned or open)
Trip Clapper (Jammed)
Trip Mechanism
Trip Sound But No Trip Trip Mechanism Trip Bar, Trip Latch (Jammed)
Pole Shaft (Jammed)
Operating Rod Assembly (Broken or pins out)
Vacuum Interrupter (One Or More Welded)
UNDESIRABLY TRIPS
Control Circuit
Control power (CS/T Switch, remains made)
Mechanism
Trip Coil Clapper (Not resetting)
Trip Bar or Trip Latch (Poor engagement of mating or worm surfaces)
Trip Bar Reset Sprint (Loss of torque)