17 Digital output module XN-322-16DO-P05
17.1 Pin assignment and status LED signals
109 XN300 slice modules 02/24 MN050002EN Eaton.com
17.1.1 Wiring topic
Four digital outputs can be wired to each of the four X1 to X4 connectors.
17.1.2 Connecting the power supply
The cross-sectional area of the +24 V cables used to supply power must be
sized for the maximum output current drawn by each group.
It is impermissible to apply a voltage, at any output, that exceeds the supply
voltage by more than 0.7 V.
The two 0 V pins on connector X5 are internally connected to each other.
17.1.3 Connecting EN 61131-2 short-circuit proof digital outputs
The outputs are able to drive twice their rated operational current briefly
when driving loads with higher inrush currents.
The outputs can be fused and switched off externally by groups by using the
corresponding group power supplies.
17.1.4 Wiring digital outputs
Figure 68: Wiring example
X1
1
2
3
4
X2
5
6
7
8
X3
9
10
11
12
X4
13
14
15
16
X5
+1
+2
0V
0V
16DO
P05
S
U
+24 V X1/X2
+24 V X3/X4