21 Multi-I/O module XN-322-16MIO-DIOAI
21.4 Technical data
XN300 slice modules 02/24 MN050002EN Eaton.com 146
21.4.5 Digital outputs
Quantity 8
Short-circuit proof as per EN 61131-2 Yes
Power supply for digital outputs
Number of supply voltages 1 (X5, pin on connector 24)
Rated operating voltage U
e
24 Vdc
Admissible range 18 – 30 VDC
Maximum permissible total current when using a duty factor of 100% 4A
Protection against polarity reversal no
Voltage monitoring Yes
Output characteristic data
„1“ signal
Output voltage (U
e
- 1V) < U
a
< U
e
Output current per channel 0.5 A
„0“ signal
Output voltage 0V
Max. output current per channel 10 A
Switching-on delay < 100 s
Configuration can be read back Yes
Signal level when reading LOW: 0 V < UE < +8 V
HIGH: +14 V < U
E < +30 V
Switch off delay
< 150 s
Maximum permissible total current for all channels when using a duty factor of 100% 4A
Maximum breaking energy of outputs (inductive load) 1 Joule/channel