21 Multi-I/O module XN-322-16MIO-DIOAI
21.4 Technical data
145 XN300 slice modules 02/24 MN050002EN Eaton.com
21.4.3 Current measurement analog input
Table 8 Technical data for analog inputs
21.4.4 Digital inputs
Channels Value
Number of channels 1
Measuring range 0…20mA 4…20mA
Measured value 0…60,000 12,000…60,000
A-D converter 16 Bit
Resolution 0.3 A / LSB
Conversion time per channel 15.26 s
Common-mode range ± 10 V
Input resistance 50
Input filters
Hardware typically 1 kHz (third-order low-pass filter)
Software (parameterizable) Configurable first-order low-pass filter
Measuring accuracy
Cumulative error ±0.5% of full scale value
Designation
Number of channels 6
61131-2 Type1
Input voltage U
E 24 Vdc maximum 30 VDC
Signal level
LOW: 0 V < UE < +5 V HIGH: +15 V < UE < +30 V
Switching threshold
normally +11 VDC
Input current at UE=24V DC normally 3.7 mA
Input delay normally 0.5 ms