EasyManua.ls Logo

Eaton XN300 - Page 153

Eaton XN300
347 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21 Multi-I/O module XN-322-16MIO-DIOAI
21.5 Memory layout
149 XN300 slice modules 02/24 MN050002EN Eaton.com
0x31C5
0x6xxA
SUB 01
1 CableBreakDiag
Open wire diagnostics
Byte 0
Bit 0 1: Cable break input U+/
U-
0x000A
Bit 1 Diagnostics possible only
in 4 to 20 mA measure-
ment range:
1: Cable break
input I+/I-
Bit 2-4 reserved
Bit 5 Measuring range
exceeded
Bit 6-7 reserved
0x4001 0x9xx0
SUB 08
max.10 CAN: SerialNumber
EC: Serialnumber
0x4004
0x8xx1
SUB 01
1 UserLEDControl
0x400C
Max.
25
ProductName
0x51C0 0x8xx6
SUB 01
1 InputChannelMode
Used to select the
measurement range
Bit 0 0: -10… +10 V
(default)
1: 0…10 V
0x0106
Bit 1 0: 0…20 mA (default)
1: 4…20 mA
Bit 2-7 reserved
0x51C1 0x8xx9
SUB 01
2 FilterConfigChannel1
Cutoff frequency setting
for low-pass filter for
current input channel 2
Used to specify the cutoff
frequency as a decimal
value in Hz.
0x0107
0x51C2 0x8xx9
SUB 02
2 FilterConfigChannel2
Cutoff frequency setting
for low-pass filter for
current input channel 2
Used to specify the cutoff
frequency as a decimal
value in Hz.
0x0109
0x51C3 0x8xxA
SUB 01
2 CableBreakLimit
Limit for open wire detec-
tion for AI2,
possible only in 0 to 20 mA
measurement range mode
Used to specify the limit
as a decimal value in A
0…4000
(default 3600)
0x010B
CAN
Object
Index
Default
CAN
Mapping
EtherCAT
Object
Index
Size
(byte)
Local I/O
description
Local I/O
addresses

Other manuals for Eaton XN300

Related product manuals