21 Multi-I/O module XN-322-16MIO-DIOAI
21.5 Memory layout
149 XN300 slice modules 02/24 MN050002EN Eaton.com
0x31C5
–
0x6xxA
SUB 01
1 CableBreakDiag
Open wire diagnostics
Byte 0
Bit 0 1: Cable break input U+/
U-
0x000A
Bit 1 Diagnostics possible only
in 4 to 20 mA measure-
ment range:
1: Cable break
input I+/I-
Bit 2-4 reserved
Bit 5 Measuring range
exceeded
Bit 6-7 reserved
0x4001 – 0x9xx0
SUB 08
max.10 CAN: SerialNumber
EC: Serialnumber
–
0x4004
– 0x8xx1
SUB 01
1 UserLEDControl –
0x400C
– – Max.
25
ProductName –
0x51C0 – 0x8xx6
SUB 01
1 InputChannelMode
Used to select the
measurement range
Bit 0 0: -10… +10 V
(default)
1: 0…10 V
0x0106
Bit 1 0: 0…20 mA (default)
1: 4…20 mA
Bit 2-7 reserved
0x51C1 – 0x8xx9
SUB 01
2 FilterConfigChannel1
Cutoff frequency setting
for low-pass filter for
current input channel 2
Used to specify the cutoff
frequency as a decimal
value in Hz.
0x0107
0x51C2 – 0x8xx9
SUB 02
2 FilterConfigChannel2
Cutoff frequency setting
for low-pass filter for
current input channel 2
Used to specify the cutoff
frequency as a decimal
value in Hz.
0x0109
0x51C3 – 0x8xxA
SUB 01
2 CableBreakLimit
Limit for open wire detec-
tion for AI2,
possible only in 0 to 20 mA
measurement range mode
Used to specify the limit
as a decimal value in A
0…4000
(default 3600)
0x010B
CAN
Object
Index
Default
CAN
Mapping
EtherCAT
Object
Index
Size
(byte)
Local I/O
description
Local I/O