23 Analog input module XN-322-7AI-U2PT
23.4 Technical data for inputs
XN300 slice modules 02/24 MN050002EN Eaton.com 166
23.4 Technical data for inputs
Number of analog input channels 7
Analog inputs 6 voltage inputs ±10 V
(of which channel 1 can be configured to work as a KTY, Pt1000 input
instead)
KTY, Pt1000 - inputs 1
Analog inputs 6
Measuring range -10V … +10V 0 – 100% (potentiometer)
Measured value -10,000…10,000 0 … 10,000
D-A converter 16 bits
Resolution 0,3 mV / LSB
Conversion time per channel 1ms
Common-mode range ± 12 V
Input resistance > 10 M
Open wire monitoring
Yes
Input filters
Hardware Typically: 1 kHz (third-order low-pass filter)
Software (parameterizable) parameterizable
Measuring accuracy
Cumulative error ± 10V ±0.3% of full scale value
Total potentiometer error ±0.35% of full scale value
KTY, Pt1000 inputs 1 (parameterizable Pt1000/KTY10)
Pt1000 KTY10
-25 … +850 °C -50 … +150 °C
502.4 – 3904.8 1035.9 – 4575.3
D-A converter 16 bits
Resolution
0.1 °C
Conversion time per channel
1 ms
Input resistance
33 k
Open wire monitoring Yes
Input filters
Hardware Typically: 1 kHz (third-order low-pass filter)
Software 10 Hz
Measuring accuracy
Basic error limit ±0.5% of full scale value