25 Analog input module XN-322-8AI-PTKT
25.7 Memory layout
187 XN300 slice modules 02/24 MN050002EN Eaton.com
0x3217 0x6401
SUB 07
0x6xx1
SUB 07
2 InputChannel7 Analog Input 7 0x008E
0x3218 0x6401
SUB 08
0x6xx1
SUB 08
2 InputChannel8 Analog Input 8 0x0090
0x3219
–
0x6xxA
SUB 01
1 CableBreakDetection Bit 0 1: Cable break Analog input 1 0x0092
Bit 1 1: Cable break Analog input 2
Bit 2 1: Cable break Analog input 3
Bit 3 1: Cable break Analog input 4
Bit 4 1: Cable break Analog input 5
Bit 5 1: Cable break Analog input 6
Bit 6 1: Cable break Analog input 7
Bit 7 1: Cable break Analog input 8
0x4001 – 0x9xx0
SUB 08
max.10 CAN:SerialNumber
EC: Serialnumber
–
0x4004 – 0x8xx1
SUB 01
1 UserLEDControl –
0x400C – –
Max.
25
ProductName –
Value Configuration InputConfig1-8
0x5210 – 0x8xx6
SUB 01
1 InputConfig1 0: Pt1000 -50 … +150°C 0x0106
0x5211 – 0x8xx6
SUB 02
1 InputConfig2 1: KTY10-62 -50 … +150°C 0x0107
0x5212 – 0x8xx6
SUB 03
1 InputConfig3 2: KTY81-110 -55 … +150°C 0x0108
0x5213 – 0x8xx6
SUB 04
1 InputConfig4 3: KTY81-121 -55 … +150°C 0x0108
0x5214
– 0x8xx6
SUB 05
1
InputConfig5 4: KTY81-122 -55 … +150°C
0x010A
0x5215
– 0x8xx6
SUB 06
1
InputConfig6 5: KTY84-1x0 -40 …+300°C
0x010B
0x5216
– 0x8xx6
SUB 07
1
InputConfig7 6: R 350 …4600
0x010C
0x5217
– 0x8xx6
SUB 08
1
InputConfig8 7: Pt100 -150 …+850°C
0x010D
Value
dec
Used to specify the cutoff frequency
for the LowPassChan1-8 channels
as a decimal value in Hz.
0x5218
–
0x8xx9
SUB 01
2 LowPassChan1 0 Filter off 0x0000 0x010E
0x5219 – 0x8xx9
SUB 02
2 LowPassChan2 10 1Hz 0x000A 0x0110
0x521A – 0x8xx9
SUB 03
2 LowPassChan3 25 25 Hz 0x0019 0x0112
CAN
Object
Index
Default
CAN
Mapping
EtherCAT
Object
Index
Size
(byte)
Local I/O
description