27 Analog output module XN-322-4AO-UI
27.6 Memory layout
XN300 slice modules 02/24 MN050002EN Eaton.com 206
0x31E0
0x6xxD
SUB 01
2 Status register
Modules Diagnostics
Bit 0 Edge limiting for analog output 1 0x0030
Bit 1 Edge limiting for analog output 2
Bit 2 Edge limiting for analog output 3
Bit 3 Edge limiting for analog output 4
Bit 4 Temperature > 142 °C, analog
output 1
Bit 5 Temperature > 142 °C, analog
output 2
Bit 6 Temperature > 142 °C, analog
output 3
Bit 7 Temperature > 142 °C, analog
output 4
Bit 8 Overcurrent at analog output 1
(voltage) Excessive voltage at
analog output 1 (current)
Bit 9 Overcurrent at analog output 2
(voltage) Excessive voltage at
analog output 2 (current)
Bit 10 Overcurrent at analog output 3
(voltage) Excessive voltage at
analog output 3 (current)
Bit 11 Overcurrent at analog output 4
(voltage) Excessive voltage at
analog output 4 (current)
Bit 12 Unable to read calibration data
Bit 13 Invalid calibration data (CRC
error)
Bit 14 DC OK on DAC
Bit 15 Offset times had to be corrected
0x4001 0x9xx0
SUB 08
max.10 CAN:SerialNumber
EC:Serialnumber
0x4004 0x8001
SUB 01
1 UserLEDControl
0x400C
Max.
25
ProductName
0x41E0 0x8xx6
SUB 01
4 OutputChannelConfig 0: deactivated
1: -10 V to +10 V voltage outputs
2: 0 to 10 V voltage outputs
3: 0 to 20 mA current outputs
0x0048
CAN
Object
Index
Default
CAN
Mapping
EtherCAT
Object
Index
Size
(byte)
Local I/O