29 Analog input/output module ±10 V XN-322-4AIO-U2
29.5 Filtering:
XN300 slice modules 02/24 MN050002EN Eaton.com 218
29.5 Filtering:
The low-pass cutoff frequency can be individually configured for each input
channel using the appropriate register. This cutoff frequency is specified in
Hz without any decimal places.
Example: 50 Hz low-pass cutoff frequency; register value: 50
dec
/ 32
hex
The following settings are valid:
Low-pass cut-off frequency Register value
Filter disabled (default) 0x0000
1 Hz 0x0001
10 Hz 0x000A
25 Hz
0x0019
50 Hz
0x0032
100 Hz 0x0064
250 Hz 0x00FA
500 Hz 0x01F4
1000 Hz 0x03E8