35 Counter module XN-322-1CNT-8DIO
35.5 Technical specifications
291 XN300 slice modules 02/24 MN050002EN Eaton.com
35.5.3 Digital outputs
Quantity 4
Short-circuit proof as per EN 61131-2 Yes
Power supply for digital outputs
Number of supply voltages 1 (X4, pin on connector 24)
Rated operating voltage U
e
24 Vdc
admissible range 18 30 VDC
Residual ripple 5%
Maximum permissible total current for all output channels when using a duty factor of 100% 6A
Protection against polarity reversal no
Output characteristic data
„1“ signal
Output voltage (U
e
- 1V) < U
a
< U
e
Output current per channel 2A
Maximum breaking energy of an output when there is an inductive load 0.65 Joule
„0“ signal
Output voltage < 0.1 VDC
Max. output current per channel 100 A
Residual current when the output has a state of "0" 12 A
Switching-on delay < 200 s
Switch off delay < 200 s
Maximum breaking energy for all outputs when there is an inductive load 1.95 Joule/channel