Tripping characteristics
43
10/13 MN03402007Z-DE/EN
Table 9: ZEB65 directly fitted or separately mounted
Table 10: ZEB150 directly fitted or separately mounted
Table 11: ZEB225A directly fitted or separately mounted
Overload relay
Fuse gG/gL [A] Rated short-circuit
current
Classifica-
tion type “1”
Classifica-
tion type “2”
I
q
[kA]
ZEB65-45 80 50 100
ZEB65-45-GF 80 50 100
ZEB65-100 100 80 100
ZEB65-100-GF 100 80 100
Overload relay Fuse gG/gL [A] Rated short-circuit
current
Classifica-
tion type “1”
Classifica-
tion type “2”
I
q
[kA]
ZEB150-100(/KK) 200 160 100
ZEB150-100-GF(/KK) 200 160 100
ZEB150-175(/KK)
ZEB150-175-GF/KK
500 500 100
Overload relay Fuse gG/gL [A] Rated short-circuit
current
Classifica-
tion type “1”
Classifica-
tion type “2”
I
q
[kA]
ZEB225A-175(/KK) 500 500 100
ZEB225A-175-GF(/KK) 500 500 100