BOOST MODE SETUP
% %
Extract
Supply
80 80
Indoor Temp (°C)
26
Relative Humidity (%)
70
CO2 (ppm)
1200
15
SUMMER BYPASS SETUP
Indoor Temp (°C)
22
Outdoor Temp (°C)
15
Unit Commissioning
3.0
The unit defaults to “Normal” mode. The ceiling
outlets should be modified in-line with the fan
speed at this part of the setup.
Note
Required flow rates per outlet should be tuned
inside of this mode
Boost mode is to be used to encourage maximum air
changes per hour (ACH), although the fan speed can
be set. Set points are also included so the unit can
automatically change into “Purge” mode if these set
points are passed
SMART mode is a unique feature to Ebac.
See section “4.4.3 SMART Mode” for further
information on the mode.
Ebac recommend that for most applications,
2 litres per day is adequate.
Once all values have been in putted, “Save Setup”.
The indoor temperature setting is the maximum
desired room temperature. This should be set to
3° above the central heating temperature
The outdoor temperature is the minimum air
temperature that the bypass will permit.
This is to prevent cold draughts.
5
6
8
7
NORMAL MODE SETUP
%
Extract
Supply
50
%
50
SMART MODE SETUP
Water Removal (L/Day)
2
Save Setup
Reset