1) ASSEMBLY
Once the area of installation is selected, mark the centre of the hole to be realized on the wall
Make sure that on internal and external walls there is enough space, for a radius of 15 cm from the centre, thus
corresponding to the product overall dimensions. Therefore make sure that, within this area, there are not any
interferences with other walls or non-removable objects.
Hole diameter for installation is:
- EBERG REQU / REQU+ / REQU R+ 160: Ø160mm
- EBERG REQU / REQU+ / REQU R+ 100 Ø100mm
The duct must be installed through the hole, with a slight downward slope of 1° - 2° towards the outsight to allow
proper discharge of condensation.
To use the supplied recessed duct, the thickness of the wall must not exceed 400mm.
To install the product, the wall thickness cannot be less than 250mm.
Once obtained the hole, put the recessed duct (6) into the wall.
Make sure that the length of the recessed duct (6) is equal to the thickness of the wall.
The duct must end with the internal and external surfaces of the wall.
The quote “M” cannot be less than 250mm. In this case the wall is not appropriate to install the product.