Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
24
When installed, the remote display must be grounded. Panel
mounting is through a 1/4 DIN cutout (see page 9). Use either the
six or ten foot cable to connect it to the motherboard.
REMOTE DISPLAY
This feature permits remote mounting of a switch to reset the Bi-
Flame. To use this feature, a normally closed remote reset switch
must be wired between terminals 1 and 4 on terminal strip J7. When
it is depressed or actuated, the connection between the terminals is
momentarily interrupted and resets the Bi-Flame. This is a low
voltage signal circuit that must be routed separately from other
control voltage wiring. Use two-conductor shielded cable with the
shield connected on one end only to terminal 1 of J7.
Note:
If reset is required from both the dispaly and the J7 terminals, use
a normally open switch.
REMOTE RESET
Warning:
Power must be off when inserting or removing
the cable.