What to do if Ecoflam MAX 15 TC J-F 115 Burner starts and then shuts down after solenoid valves open?
- TTammy RomeroAug 11, 2025
If your Ecoflam Burner starts but shuts down after the solenoid valves open, it indicates no flame signal at the end of the safety time. First, ensure the oil level in the tank is adequate and the valves are open. Then, examine the oil pressure, pump operation, coupling, filter, and solenoid valve. Next, check the ignition circuit and electrode adjustment, cleaning or replacing electrodes as necessary. Finally, clean or replace the flame monitor. If problems persist, consider replacing ignition electrodes, ignition cables, the ignition transformer, nozzle, pump, solenoid valve, or the automatic combustion control unit as needed.