EasyManuals Logo

Ecolink Z-Wave TBZ500 User Manual

Ecolink Z-Wave TBZ500
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
Config
Parameter
#
Description
Length
(bytes)
Send
Unsolicited
on
change
Default
Value
Read values
Write values
18
C Delta Stage 1 OFF
1
N
0
0-5
0-5
19
C Delta Stage 2 ON
1
N
2
2-7
2-7
20
C Delta Stage 2 OFF
1
N
0
0-6
0-6
21
Mechanical Status
3
2
Y
MECH_H1 0x0001
MECH_H2 0x0002
n/a
0x15
MECH_H3 0x0004
MECH_C1 0x0008
MECH_C2 0x0010
PHANTOM_F 0x0020
MECH_F 0x0040
MANUAL_F 0x0080
Reserved 0x0100
22
SCP Status
3
1
Y
STATE_HEAT 0x01
STATE_COOL 0x02
n/a
0x16
STATE_2
ND
0x04
STATE_3
RD
0x08
STATE_FAN 0x10
STATE_LAST 0x20
STATE_MOT 0x40
STATE_MRT 0x80
23
Autosend Enable Bits
2
N
0x205F
TEMPERATURE
(CC_SENSOR_MULTILEVEL)
0x0001
0x17
SETPOINTH
(CC_THERMOSTAT_SETPOINT)
0x0002
When set, the
corresponding
SETPOINTC
(CC_THERMOSTAT_SETPOINT)
0x0004
report is sent out
unsolicited
MODE
(CC_THERMOSTAT_MODE)
0x0008
when a changed is
detected, to
FANMODE
(CC_THERMOSTAT_FAN_MODE)
0x0010
the nodes in the
association list
FANSTATE (CC_THERMOSTAT_FAN_STATE) 0x0020
OPERATINGSTATE (CC_THERMOSTAT_OPERATING_STATE) 0x0040
SCHEDENABLE (CC_CONFIGURATION #38) 0x0080
SETBACK (CC_CONFIGURATION #40) 0x0100
RUNHOLD (CC_CONFIGURATION #39) 0x0200
DISPLAYLOCK (CC_CONFIGURATION #24) 0x0400
0x0800
0x1000
BATTERY
6
(CC_BATTERY) 0x2000
MECH STATUS (CC_CONFIGURATION #21) 0x4000
SCP STATUS (CC_CONFIGURATION #22) 0x8000
24
Display Lock
3
1
Y
0
0 = unlocked
0 = unlocked
1 =locked
1 = locked

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ecolink Z-Wave TBZ500 and is the answer not in the manual?

Ecolink Z-Wave TBZ500 Specifications

General IconGeneral
BrandEcolink
ModelZ-Wave TBZ500
CategoryThermostat
LanguageEnglish