Installation and Operating manual
Econ
®
Series 3300 Smart Valve Positioner www.eriks.com www.eriks.com
29
6.3.5.5 Tight Shut Close (TSHUT CL)
Tight Shut Close allows the valve to close completely as the input signal reaches around
4mA.
6.3.5.6 Split Range Mode (SPLIT)
The valve can be operated by split range control 4~12mA or 12~20mA.
6.3.5.7 Custom Zero Setting Mode (CST ZERO)
Custom Zero Setting Mode allows the user to set any specific point as zero position. For
example, the zero point can be set at input signal of 7mA.
<ENTER>
6 seconds
<DOWN>
4 times
<ENTER>
<UP>/<DOWN>
<ESC>
3 times
<ENTER>
<ENTER>
6 seconds
<DOWN>
5 times
<ENTER>
<UP>/<DOWN>
<ESC>
3 times
<ENTER>
<ENTER>
<DOWN>
6 times
<ENTER>