Installation & Operation Manual Proven Quality since 1892
ECON actuator Fig. 7907, type ELA80 3000 www.eriks.com
Rev.23 August, 2023 36
5.5 Operations
Local Operation
1. Put the selector switch into Local Mode.
2. Use the open/close switch to operate the actuator.
3. In Local Mode the LED indicators will show the below status:
RED LED ON : Fully Open
GREEN LED ON : Fully Close
RED or Green LED Blinking : Opening or closing
Remote (Manual mode) Operation
1. Put the selector switch into Remote Mode.
2. Manual Mode is functional if terminal strip number 5 and 9 are NOT wired.
3. In Manual Mode the LED indicators will show the below status:
BLUE LED Steady ON : Manual mode
For wiring diagrams see drawings D7907-3 RBP and D7907-4 RBP on page 41-49
Remote (Modulating mode) Operation
1. Put the selector switch into Remote Mode.
2. Modulating Mode is functional if terminal strip number 5 and 9 are wired.
3. In Modulating Mode the LED indicators will show the below status:
BLUE LED Blinking: Modulating mode
4. For actuator operation please refer to the paragraph 4.10 (PCU settings).
For wiring diagram see drawing D7907-4 RBP+PCU on page 50
Battery Mode Operation
1. If the power supply has been switches off, the actuator will be powered by the battery.
2. LOCAL MODE: Operate the Open/Close switch in order to put the actuator in the open or closed p
osition.
3. REMOTE MODE: During power failure, the actuator will follow the power failure settings (DIP
switch settings see paragraph 4.12.4)
4. NO FAIL ACTION : The actuator will operate the same way as if there was not power failure.