EasyManua.ls Logo

ECOSTAR ECO 30 - Maintenance

Default Icon
47 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
02.12.2022 Rev. 12
40
8.11. Gas Pass Equipment Required in Gas Line
Pe < 300 mbar
Q<1200kW
Pe > 300 mbar
Q<1200kW
Pe < 300 mbar
Q>1200kW
Pe > 300 mbar
Q>1200kW
1- Compensator 1- Compensator 1- Compensator 1- Compensator
2- Ball valve 2- Ball valve 2- Ball valve 2- Ball valve
3- Gas filter 3- Gas filter 3- Gas filter 3- Gas filter
4- Inlet manometer + valve 4- Inlet manometer + valve 4- Inlet manometer + valve 4- Inlet manometer +
valve
8 – Multi-block (safety and
operation solenoids)
5- Regulator 8 – Multi-block (safety and
operation solenoids))
5- Regulator
9- Sealing Control Set 6- Outlet manometer + valve
9- Sealing Control Set 6- Outlet manometer +
valve
7- Safety discharge valve 7- Safety discharge valve
8 – Multi-block (safety and
operation solenoids)
8 – Multi-block (safety
and operation solenoids)
9- Sealing Control Set 9- Sealing Control Set
Threaded and flanged connections may vary depending on the gas pressure and consumption.