3. BURNERS GENERAL FEATURES
ECOSTAR Dual Fuel (Gas-Light Oil) burners are designed and manufactured to work with liquid
fuel with max. 2.5- 6 Cst (mm
2
/
s) viscosity. and Natural Gas and Liquid Petroleum Gas at gas pressures
of min.20 mbar, max.300 mbar and at -%15 to +%10 of nominal voltages, under environmental
temperature of max.60˚C with rated capacity and burner pressure ranges.
3.1. Purpose of Use and Work Limits of Burners
This product works at any load value equivalent to its max. capacity or covered by its capacity
range;
- In hot water and steam boilers,
- In direct and indirect hot air generators,
- Industrial appliances operating at temperature below 600
0
C,
- -15
0
C…+60
0
C ambient temperature range,
- 1N 230 VAC/3N 380VAC /50 Hz feed voltage (-%15…+%10) values,
- Max. 95% relative humidity,
- In well-ventilated open and closed spaces compatible with protection class IP 40.
This device must never be operated with open flame!