POWER INVERTER – MI-/TMI-SERIES
]
43
The inverter disconnects the AC output in the following cases:
internal temperature too high
required output load too high
input voltage too high or too low
Reason 12 V 24 V 48 V Action
risk of under-
voltage
10.5V±0.5V 21.0V±1.0V 42.0V±2.0V 2x acoustic signal
+ red LED flashing 2x
every 8 sec.,
inverter still working
total undervolt-
age
10.0V±0.5V 20.0V±1.0V 40.0V±2.0V 3x acoustic signal
+ red LED flashes 3x
every 8 sec.,
automatic shutdown
overvoltage 15.0V±0.5V 30.0V±1.0V 60.0V±2.0V 4x acoustic signal
+ red LED flashing 4x
every 8 sec.,
automatic shutdown
overheating internal temperature >75°C 5x acoustic signal
+ red LED flashes 5x
every 8 sec.,
automatic shutdown
overload due
to powerful
consumers
regardless of the type 11x acoustic signal
+ red LED flashes con-
stantly until the error
is solved and device is
switched on again
short circuit of
consumers
regardless of the type red LED flashes
constantly until error
is solved and device is
switched on again
polarity reversal regardless of the type the fuses blow
undervoltage
ECO-Mode
11V±0.2V 22V±0.4V 44V±0.8V shift to mains priority