Page 3 of 4 DATA SHEET E85001-0279
Not to be used for installation purposes. Issue 1
Figure 2. SIGA-270, SIGC-270F, SIGC-270B installation
Figure 3. SIGA-270P, SIGC-270PB installation
Installation
Single-stage Signature Series fire alarm manual pull stations mount to North American 2½ inch (64 mm) deep 1-gang boxes.
Two stage presignal (270P) models require 1½ inch (38 mm) deep 4-inch square boxes with 1-gang, ½-inch raised covers. Openings
must be angular. Rounded openings are not acceptable. Recommended box: Steel City Model 52-C-13; in Canada, use Iberville Model CI-
52-C-49-1/2.
All models include terminals are suited for #12 to #18 AWG (2.5 mm
2
to 0.75 mm
2
) wire size. EDWARDS recommends that these fire
alarm stations be installed according to latest recognized edition of national and local fire alarm codes.
Electronic Addressing: The loop controller electronically addresses each manual station, saving valuable time during system com-
missioning. Setting complicated switches or dials is not required. Each station has its own unique serial number stored in its on-board
memory. The loop controller identifies each device on the loop and assigns a “soft” address to each serial number. If desired, the stations
can be addressed using the SIGA-PRO Signature Program/Service Tool.
Figure 1. SIGA-278 installation
L
IF
T
NORMAL
Cover Release
Screw
Compatible
Electrical Box
with ½-inch
raised covers
Glass Rod
Release Lever
Toggle
Switch
Back
Plate
Do not use
boxes with
rounded
openings.