Chapter 1: Product design
SIGA-REL Technical Reference Manual 11
Abort circuit, TB3-3 and TB3-4
Line resistance
End of line device
Circuit capacitance
Supervision
Ground fault impedance
25 /wire, 18 AWG = 3,800 ft (0.75 sq mm = 1,158 m)
47 k resistor
0.1 F, max.
Open and ground
0.0 Ω
Zone relay output, TB2
UL rating
Type
Contact rating:
Supervision
Zone
Form C
3 A at 24 VDC, (resistive load)
Not supervised
Signature data line, TB1
Operating voltage
Supervisory current
Alarm current
Line resistance
Maximum quantity
15.2 to 19.95 VDC
1 mA
1 mA
See the installation sheet for the Signature loop controller
10 SIGA-REL modules per loop
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing
[1] Riser current: The total current of the prerelease and release circuits is limited to 3.83 A. This
is the power riser maximum input current of 4 A, minus 170 mA.
Table 7: Power riser
Distance from SIGA-REL to power supply
[1] Wire resistance measured in Ω per wire
Table 8: Prerelease and release circuits (per circuit)
Distance from SIGA-REL to signals