EasyManua.ls Logo

Edwards SIGA-REL Technical

Edwards SIGA-REL Technical
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 1 Product design
12 SIGA-REL Technical Reference Manual
Total riser
current (A)
Distance from SIGA-REL to signals
Wire
resistance [1]
12 AWG
2.5 sq mm
14 AWG
1.5 sq mm
1.25
282 ft
85.95 m
192 ft
58.52 m
0.480
1.00
353 ft
107.59 m
240 ft
73.15 m
0.600
0.50
706 ft
215.19 m
480 ft
146.30 m
1.200
[1] Wire resistance measured in Ω per wire
Table 9: Compliance requirements
Item
Requirement
Power riser
When two or more SIGA-REL modules are powered from a
single riser, those SIGA-REL modules must be in the same
notification zone.
NAC synchronization
UL 864 requires synchronization of notification appliances when
they are in the same notification zone. This means that when
more than one SIGA-REL is installed, the audible and visible
notification appliances controlled by each SIGA-REL must
operate in separate notification zones. The notification
appliance output from two SIGA-REL modules cannot be
audible or visible within the same notification zone.
Evacuation tone
The SIGA-REL is not designed to generate an NFPA 72
standard alarm evacuation signal, and does not meet UL 864
requirements for audible alarm notification circuits intended for
evacuation. Notification zones must include additional NACs
and appliances capable of producing the required evacuation
tone to meet these requirements.
Horns
Horn signaling patterns are controlled by the SIGA-REL, so
configurable horns must be set for steady output.
Manual release station
The manual release station controls only the SIGA-REL to
which it is connected.
When using NFPA 12A and NFPA 2001 suppression agents, a
separate, mechanical manual release is required in addition to
the release station connected to the SIGA-REL.
Abort station
The abort station controls only the SIGA-REL to which it is
connected. However, activation of the abort switch must be
annunciated at all panels in a network.
UL 864 allows only one abort station per suppression area. This
means you cannot install more than one SIGA-REL per
suppression area.
Zone relay output
Zone relay output contacts cannot be used for a notification
appliance circuit or a nonaddressable signaling line circuit.
Service disconnect station
Activation of the service disconnect must be annunciated as a
supervisory event at all panels in a network.