Chapter 3: Programming
SIGA-REL Technical Reference Manual 45
2. Enter the following information:
First address
Device type: Output
Model: REL
Personality: (16) Output B
Message text: SIGA-REL1 A003 and RELEASE 1 & 2
Second address
Device type: Monitor
Personality: (0) None
Message text: SIGA-REL1 A004 and NOT USED
3. Click Add.
Step 4: Add the two prerelease circuits
1. Set the Quantity box to 1.
2. Enter the following information:
First address
Device type: Output
Model: REL
Personality: (16) Output B
Message text: SIGA-REL1 A005 and PRERELEASE 1 & 2
Second address
Device type: Monitor
Personality: (0) None
Message text: SIGA-REL1 A006 and NOT USED
3. Click Add.
Table 20 shows how your entries in the Modules table should look. Your
addresses may be different.
Table 20: SIGA-REL configuration settings
Address
Serial
number
Device
type
Model
Text 1
Text 2
Personality
126
Monitor
REL
SIGA-REL1
A001
ABORT SW
(3) Active B
127
Pull
REL
SIGA-REL1
A002
MAN RELEASE
(1) Alarm B
128
Output
REL
SIGA-REL1
A003
RELEASE 1 & 2
(16) Output B