Chapter 3: Programming
46 SIGA-REL Technical Reference Manual
Address
Serial
number
Device
type
Model
Text 1
Text 2
Personality
129
Monitor
REL
SIGA-REL1
A004
NOT USED
(0) None
130
Output
REL
SIGA-REL1
A005
PRERELEASE 1 &
2
(16) Output B
131
Monitor
REL
SIGA-REL1
A006
NOT USED
(0) None
Step 5: Create a prerelease response
In this step, you create a response that activates the prerelease circuits when
any one detector in the protected area signals an alarm.
1. Click Configure > Correlations.
2. Click the Zones tab, and then click Add Zones.
3. Click the Members tab, and then click Add Device.
4. Select only the devices required to activate the SIGA-REL prerelease circuits,
and then click OK.
5. Click the Responses tab, click the Response Type arrow, and then select
Active.
Caution: Do not include the releasing circuits (RELEASE 1 & 2) in this response.
6. Click Outputs, select the device labeled SIGA-REL1 A005 PRERELEASE 1 &
2, and then click OK.
Make sure you select the PRERELEASE device, not the RELEASE device.
Step 6: Create an AND group release response
Here, you create a release response that activates the release circuits when two
or more detectors in the protected area signal an alarm.
Note: To comply with NFPA 72, you must program an AND Group with at least
two smoke detectors and a minimum activation count of 2. The smoke detectors
must have their Primary and Alternate Verification properties set to None (verified
smoke detectors are not allowed).
1. Click the AND Groups tab, and then click Add AND Group.
2. Set the Activation Count box for 2.
3. Click the Members tab, and then click Add Device.