MANUAL Alarm index
EVO
45
Fault message Fault cause Remedy
11/15
80
High pressure transducer refrigerant
circuit defective!
-control wire defect or broken.
-pressure transducer outside of the range.
-pressure transducer is defective.
-check it terminals are tight.
-locate loose contact and solve it.
-check wire for a defect.
-replace pressure transducer.
81
Low pressure transducer refrigerant
circuit defective!
-control wire defect or broken.
-pressure transducer outside of the range.
-pressure transducer is defective.
-check it terminals are tight.
-locate loose contact and solve it.
-check wire for a defect.
-replace pressure transducer.
85
defective!
-control wire defect or broken.
-temperature probe outside of the range.
-temperature probe is defective.
-check it terminals are tight.
-locate loose contact and solve it.
-check wire for a defect.
-replace temperature probe.
86
Temperature probe evaporator outlet
defective!
-control wire defect or broken.
-temperature probe outside of the range.
-temperature probe is defective.
-check it terminals are tight.
-locate loose contact and solve it.
-check wire for a defect.
-replace temperature probe.
87
OPTION
Temperature probe reference
defective!
-control wire defect or broken.
-temperature probe outside of the range.
-temperature probe is defective.
-check it terminals are tight.
-locate loose contact and solve it.
-check wire for a defect.
-replace temperature probe.
1
Low pressure alarm refrigerant circuit!
-leak in the refrigeration system
-loos of refrigerant.
-expansion valve is defective.
-solenoid valve is defective.
-check if terminals are tight.
-call ef cooling to find e solution.