4.2 Ambient conditions for assembly
To guarantee perfect operation and a long service life, assemble the
photovoltaic solar inverter in accordance with the following requirements.
Select the coolest possible location for assembly.
High temperatures hamper the effectiveness and shorten the service
life of the photovoltaic solar inverter. If need be, install an additional
cooling system in the room in which the photovoltaic solar inverter is
assembled.
When assembling the photovoltaic solar inverter, the ambient
temperature must be in the range from - 25 °C to + 50 °C.
1 – 25 °C
2 + 50 °C
Fig. 4-2 - 1 Ambient conditions for assembly (temperature)
Relative humidity 0 % to 90 % (without condensation)
The photovoltaic solar inverter may not be exposed to any direct
solar radiation.