EasyManuals Logo

Ei Electronics Ei262 User Manual

Ei Electronics Ei262
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
CO Alarm Memory: : A unit will indicate if it has been in alarm previously by flashing the red light
for 2 seconds every 40 seconds (2 flashes for 50 ppm CO, 4 flashes for
100 ppm CO and 8 flashes, for 300 ppm CO). When the Test/Hush button
is pressed, the red light flashes (as per Table B on page 8) to indicate the
previous CO alarm level detected. The memory is cleared by holding down
the Test/Hush button until the red light stops flashing.
Repeater Function : To disable the Repeater function press and hold the Test/Hush button
until the alarm sounds and the red RadioLINK light turns on. Immediately
(while the red RadioLINK light is still on), press and hold the House Code
switch with a small screwdriver, until the red indicator light gives 3 slow
flashes. Immediately release the House Code switch and Test/Hush button.
To re-activate the Repeater function just follow the instructions above for
disabling. The RadioLINK light will flash 15 or 16 times and stop to show
the Repeater function is now activated.
Dimensions : 126 x 150 x 42 mm. Weight: 330g.
32

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ei Electronics Ei262 and is the answer not in the manual?

Ei Electronics Ei262 Specifications

General IconGeneral
BrandEi Electronics
ModelEi262
CategorySecurity System
LanguageEnglish

Related product manuals