5-19
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-02Service Manual - Delta DCI
5.6.7 Model: Delta 50 DCI Cooling – Test Mode
Suction Pressure VS. Outdoor Temp.
400
500
600
700
800
900
1000
1100
1200
10 15 20 25 30 35 40 45
Outdoor DB TemperatureC]
Suction Pressure [kPa]
22/15 DB/WB
24/17 DB/WB
27/19 DB/WB
29/21 DB/WB
32/23 DB/WB
Discharge Pressure VS. Outdoor Temp.
1000
1250
1500
1750
2000
2250
2500
2750
3000
3250
3500
3750
4000
10 15 20 25 30 35 40 45
Outdoor DB Temperature [ºC]
Discharge Pressure [kPa]
22/15 DB/WB
24/17 DB/WB
27/19 DB/WB
29/21 DB/WB
32/23 DB/WB