DNG series
REFRIGERANT
R410A
HEAT PUMP
COOLING ONLY
FEBRUARY 2005
Indoor Units Outdoor Units
DNG 18 GC18
DNG 24 OU7-24
DNG 30 OU8-30
DNG 37 OU10-36
DNG 44 OU10-44
Service Manual

Questions and Answers

  • G
    Gary NelsonAug 9, 2025
    What to do if the operation indicator does not light up when starting my Electra Heat Pump from the unit?
    • T
      Tammy SantiagoAug 9, 2025
      If the operation indicator (green LED) on your Electra Heat Pump doesn't light up when starting from the unit, it may be an issue with the main P.C.B or display P.C.B. If necessary, replace the P.C.B.
  • J
    Jasmin SmithAug 22, 2025
    How to fix stand-by indicator if it doesn't light up on Electra Heat Pump?
    • D
      Dana JonesAug 23, 2025
      If the stand-by indicator (red LED) on your Electra Heat Pump's central control display panel doesn’t light up, it could be due to several reasons: - There might be no correct voltage between the line and neutral terminals on the main P.C.B. If the voltage is low, repair the power supply. If there is no voltage, repair the general wiring. If there is correct voltage, replace the main or display P.C.B’s.

Electra DNG 18 Specifications

General IconGeneral
ModelDNG 18
Heating Capacity18 kW
Cooling Capacity16 kW
RefrigerantR410A
TypeAir to Water Heat Pump
Power Supply400V, 3-phase, 50Hz