10. SETTINGS MENU
To access the settings menu press and hold the SETUP key for 3 seconds.
LANGUAGE
0=ITA / 1=ENG / 2=FRA / 3=ESP / 4=DEU
DISPLAY BRIGHTNESS ON STANDBY
This parameter allows to enter the brightness setting applied when the
display is set to standby (wait 9 seconds for a preview).
KLIXON SELF-RESET
This parameter defines the automatic or manual reset of the motor
overtemperature alarm from Klixon.
ESPANSIONE POMPE
This parameter defines whether the system provides the card for the 3rd
and 4th pump.
MINIMUM VOLTAGE
Set by default to -10%. (Altering operating limits beyond default
parameters will immediately render the warranty null and void).
MAXIMUM VOLTAGE
Set by default to +10%. (Altering operating limits beyond default
parameters will immediately render the warranty null and void).
MOTOR M1– M4 MAXIMUM CURRENT
This parameter allows the maximum current limit of the motor to be set.
Enter the maximum current value, increasing it by 10-15% with respect to
the rated motor value.
Altering operating limits beyond the parameters stated on the model data
plate will immediately render the warranty null and void.
MINIMUM CURRENT OR COS-FI CONTROL ACTIVATION
This parameter allows the dry run control to be enabled by reading the
absorbed motor current value or the cos-fi power factor.