The detected minimum current value is lower than the programmed
value and the panel stops the motor.
The display and the red LED flash, activating the cumulative alarm
output and the "BUZZ" output.
The system resets automatically according to the times set during
programming.
The alarm can still be reset manually by pressing the OFF key; the
system can then be reset automatically.
The motor current absorption is higher than the set value and the panel
stops the relevant motor.
The display and the red LED flash, activating the cumulative alarm
output and the "BUZZ" output.
To reset the alarm manually, press the OFF key; the system can then be
reset automatically.
The thermal switch (Klixon) has tripped on overtemperature.
The display and the red LED flash, activating the cumulative alarm
output and the "BUZZ" output.
If Klixon self-reset is activated, the system automatically resets when
the Klixon contact is closed; if the self-reset is disabled, when the Klixon
contact is closed, press the "AUT" key and then restart the individual
motors in alarm with "MAN".
If not used, close the motor Klixon input/s.
The measured mains voltage is too low (the motor stops).
The display and the red LED flash, activating the cumulative alarm
output and the "BUZZ" output.
The system is reset automatically when voltage increases.
The measured mains voltage is too high (the motor stops).
The display and the red LED flash, activating the cumulative alarm
output and the "BUZZ" output.
The system is reset automatically when voltage decreases.