5.4
Installation and operation
using an anemometer.
Do not connect cool air inlet ducts directly to the
compressor inlet side.
To eliminate transmission of vibrations, provide a soft
bellows connector between the duct and the compressor.
Contact ELGi in case you need to provide a duct
connection or filter fitment on the compressor.
5.1.5 Electricals
Figure 6. Forced ventilation with exhaust fan
Figure 7. Ventilation with ducts
Ensure that only authorized service technicians perform
electrical work. Study the electrical circuit diagram before
starting work.
Model
Minimum
ventilation
requirement
(ft
3
/h )
Minimum
ventilation
requirement
(m
3
/h)
EG 11 94,537 2,677
EG 15 128,086 3,627
EG 18 157,185 4,451
EG 22 204,154 5,781
EG 30 242,576 6,869
EG 37 299,185 8,472
EG 45 363,847 10,303
EG 55 464,246 13,146
EG 75 631,708 17,888
EG 90 705,481 19,977
EG 110 864,821 24,489
EG 132 1,033,801 29,274
EG 160 1,273,482 36,061
EG 200 1,718,976 48, 676
EG 250 1,718,976 48, 676
EG 90-P 708,765 20,070
EG 110-P 1,218,356 34,500
EG 132-P 1,218,356 34,500
EG 160-P 1,218,356 34,500
Table 1. Global series – Ventilation requirements
Model
Motor power Back up fuse
Incoming Cable
size
Incoming Cable size Earth cable Gland Size
kW H.P
208 -
230V
460V
Cu
Sq.mm
Al
Sq.mm
Cu Sq.mm Al Sq.mm Size Dia
EG 11 11 15 100A 63A 4 X 10 4 X 16 4 X 4 4 X 6 2.5 Gauge 25 mm
EG 15 15 20 100A 63A 4 X 16 4 X 25 4 X 6 4 X 10 2.5 Gauge 25 mm
EG 18 18 25 125A 63A 4 X 25 4 X 35 4 X 6 4 X 10 2.5 Gauge 25 mm
EG 22 22 30 160A 63A 4 X 35 4 X 50 4 X 10 4 X 16 4 Gauge 28 mm
EG 30 30 40 200A 100A 4 X 50 4 X 70 4 X 16 3 1/2 X 25 4 Gauge 32 mm
EG 37 37 50 250A 125A 4 X 70 4 X 95 3 1/2 X 25 3 1/2 X 35 6 Gauge 35 mm
EG 45 45 60 125A 3 1/2 X 35 3 1/2 X 50 6 Gauge 35 mm
EG 55 55 75 160A 3 1/2 X 35 3 1/2 X 50 6 Gauge 35 mm
EG 75 75 101 250A 3 1/2 X 70 3 1/2 X 95 8 Gauge 50 mm
EG 90 90 121 250A 3 1/2 X 70 3 1/2 X 95 8 Gauge 50 mm
EG 110 110 147 315A 3 1/2 X 95 3 1/2 X 120 25 x 3 cu flat 1.75 inch
EG 160 160 214 400A 3 1/2 X 150 3 1/2 X 185 35 x 3 cu flat 2.25 inch
Table 2. Global series – Electrical requirements