The EWPC 961 is a temperature
controller specifically designed for
refrigeration applications and pro-
vides time control for off-cycle de-
frost management.
GENERAL DESCRIPTION
The EWPC 961 is a temperature controller
specifically designed for refrigeration appli-
cations and provides time control for off-
cycle defrost management.
It incorporates an output relay for com-
pressor control and a PTC sensor input.
A number of parameters are displayed al-
phanumerically to set up the instrument for
each specific application.
The EWPC 961 is supplied in the popular
“32x74” ELIWELL.
OPERATION
The EWPC 961 is designed to operate
strictly as a cooling control, which means
that the switching differential is positive:
the compressor cuts off at setpoint and is
started at a temperature of set plus differ-
ential. The on-board microprocessor pro-
vides several timing functions for the
defrost; the defrost cycle as well the de-
frost cycle duration are user selectable.
At the start of each defrost cycle, the com-
pressor is simply stopped, regardless of
the temperature control circuit.
In addition, the EWPC 961 offers several
system protection features, all easy to un-
derstand and easy to program.
FRONT KEYPAD
SET: push to display the setpoint temper-
ature; the “DEF/SET” status light will blink.
The setpoint can be changed within 5 sec-
onds with the “UP” or “DOWN” button.
The control will automatically switch back
to normal operating mode within 5 sec-
onds; the last entered setpoint will stay in
memory.
UP: used to increase the setpoint value, as
well as the parameter when in program-
ming. When held down for a few seconds,
the change rate accelerates.
DOWN: same functions, except to de-
crease a value.
DEFROST: push to initiate a manual de-
frost cycle (override of programmed de-
frost start; programmed time resets to
zero). Manual defrost can not be started
while in setpoint or in parameter program-
ming mode. This button must be activated
for 3 seconds to start a defrost; the
“DEF/SET” status light will come on and
the compressor is stopped.
Led “COMP”: status light of the compres-
sor output.
Led “DEF/SET”: blinks during setpoint
display/change. When Led is on the de-
frost is in progress.
PARAMETER PROGRAMMING
Programming is easily accessed by hold-
ing the “SET” button down for more than
4 seconds; the first parameter is displayed
while the status light “DEF/SET” remains
blinking during the programming period.
Other parameters are accessed with the
“UP” and “DOWN” button.
With the “SET” button, the actual setting of
each parameter is displayed. To change a
parameter setting, push the “SET” plus the
“UP” (or “DOWN”).
The system will automatically return to its
normal operating mode a few seconds af-
ter the programming procedure is com-
pleted or interrupted.
DESCRIPTION OF PARAMETERS
d: differential.
LS: Lower Set.
Setting of the lower user-access setpoint
limit.
HS: Higher Set.
Setting of the upper user-access setpoint
limit.
CA: CAlibration.
Temperature read-out offset to allow for
possible error due to probe location.
rP: relay Protection.
Select relay status in case of probe defect.
on = compressor ON in case of probe de-
fect;
HOW IT IS MADE
Housing: black ABS plastic, self-
estinguishing
Dimensions: front 74x32 mm
(2.913x1.260"), depth 67 mm
(2.637")
Protection: the instrument front-
panel is waterproof IP65; an op-
tional snap-on cover can be
supplied to provide additional pro-
tection of the rear terminal block
Connections: screw terminal
block (2.5 mm
2
; one wire each ter-
minal onl)
Display: 12.5 mm LED (0.50")
Push buttons: located on front
panel
Output: one (1) SPDT relay 8(3)A
250Va
Input: PTC probe
Resolution: 1 °C (°F)
Accuracy: better than 0.5% of full
scale
Power supply (depending on mod-
el): 12 Va/c or 24 Va/c
WHAT IT IS
EWPC 961
freezer controls
Question and Answer IconNeed help?

Do you have a question about the Eliwell EWPC 961 and is the answer not in the manual?

Summary

General Description and Purpose

Device Operation Modes

Front Keypad Functions

Controls for user interaction, including setpoint adjustment and manual defrost initiation.

Parameter Programming Access

Process for accessing and modifying device settings and operational parameters.

Standard Model Default Settings

Electrical Connections and Wiring

Installation Guidelines

Error Indication and Troubleshooting

Technical Specifications

Document Disclaimer

Summary

General Description and Purpose

Device Operation Modes

Front Keypad Functions

Controls for user interaction, including setpoint adjustment and manual defrost initiation.

Parameter Programming Access

Process for accessing and modifying device settings and operational parameters.

Standard Model Default Settings

Electrical Connections and Wiring

Installation Guidelines

Error Indication and Troubleshooting

Technical Specifications