display
description
Enables or disables a warning buzzer for alarm conditions.
Door open alarms alwayssound the warning buzzer.
considerations
Following alarm conditions trigger the buzzer:
l
refrigeration system failure (rSF)
l
sensor failure (PF1, PF2, and PF3).
l gas cooler high temperature alarm
l CO2 lock out alarm
Door alarms sound the buzzer as standard.
range 00 (disabled) or 01 (enabled)
global default 01 (enabled)
10.7 buzzer duration (b1)
The table below details the buzzer duration (b1) parameter.
display
description
Defines the duration of the buzzer for door open alarm conditions.
If the door remains open after the buzzer duration (b1), the ems controller switches off the compressor.
considerations
The ems controller switches off the compressor after the duration defined by alarm delay (Ad) + buzzer
duration (b1).
range 1 to 254 seconds
global default 60 seconds
10.8 calibration 1 (CA1)
The table below details the calibration 1 (CA1) parameter.
display
description Calibrates or adds an offset to temperatures measured by the appliance sensor.
considerations Applied to all temperatures measured on the appliance sensor.
range -9.9 to 9.9°C (-18 to 18°F)
global default 0.0°C (0°F)
10.9 calibration 2 (CA2)
The table below details the calibration (CA2) parameter.
ems55advanced and ems55Radvanced / General Use
69 of 84