10.27 high voltage (HI)
The table below details the high voltage (HI) parameter.
display
description
Defines the maximum voltage allowed before switching off the compressor.
The high voltage (HI) values are approximations and not actual voltage readings (see table below).
considerations
1. Must not be used with an external voltage stabiliser
2. Must only be used with an elstat supplied transformer
3. Only used with ems55advancedand ems55Radvanced
range 180 to 250 (not Vac)
global default 250 (disabled)
100V line 110-120V line 220-240V line
voltage HI voltage HI voltage HI
110 180 139 180 230 190
114 185 142 185 235 195
118 190 145 190 240 200
122 195 148 195 245 205
250 210
255 215
260 220
note: Voltage measurement is accurate to ±10%. 265 225
Caution:
l High voltage protection is not calibrated and actual performance can be influenced by several factors.
Therefore, total protection cannot be guaranteed.
10.28 condenser high temperature (Ht)
The table below details the condenser high temperature (Ht) parameter.
display
description
Defines the maximum temperature measured in the refrigeration system by
monitoring the condenser sensor.
On reaching the condenser high temperature (Ht), the ems controller disables
the compressor and activates an alarm.
considerations
1. Is not used with CO2 (R744) coolers.
ems55advanced and ems55Radvanced / General Use
76 of 84