2. Must only be used with an elstat supplied transformer
3. Only used with ems55advancedand ems55Radvanced
range 90 to 160 (not Vac)
global default 90 (disabled)
100V line 110-120V line 220-240V line
voltage LO voltage LO voltage LO
79 120 95 120 173 130
81 125 98 125 178 135
84 130 100 130 182 140
87 135 103 135 187 145
90 140 106 140 192 150
197 155
Note: Voltage measurement is accurate to ±10%. 203 160
Caution:
l Low voltage protection is not calibrated and actual performance can be influenced by several factors.
Therefore, total protection cannot be guaranteed.
10.32 learning period (LP)
The table below details the learning period (LP) parameter.
display
description Defines whether the ems controller uses a 1-day or a 7-day learning period.
considerations None
range 00 (1 day) or 01 (7 days)
global default 00 (1 day)
10.33 saving temperature disable (PEr)
The table below details the saving temperature disable (PEr) parameter.
display
description
Disables the saving mode temperature so that the ems controller maintains the ready mode temperature
at all times.
Disabling the saving mode temperature does not affect the light functionality.
ems55advanced and ems55Radvanced / General Use
78 of 84

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Elstat ems55Radvanced and is the answer not in the manual?

Elstat ems55Radvanced Specifications

General IconGeneral
BrandElstat
Modelems55Radvanced
CategoryController
LanguageEnglish

Related product manuals