User’s Guide FlatpackS Rectifier & Supervision Modules, 7
3. Installation of Flatpack2 Modules
Installing Rectifiers, Controller and Blind Panels
Removing Flatpack S Rectifiers
To remove the
Flatpack S
rectifiers, do following:
Unlock the rectifier
by
using a screwdriver to turn the locking screw ¼ of a turn
clockwise to the unlocked position (
)
Remove the rectifier
by
using the rectifier’s handle to pull the module loose. Support
from underneath before the unit is completely free
Mount blind panels
in
unused rectifier locations
Mounting Flatpack S Rectifiers
To mount the
Flatpack S
rectifiers, do following:
Unlock the rectifier
by
using a screwdriver to turn the locking screw ¼ of a turn clockwise to
the unlocked position (
)
Notice
: the rectifiers may be inserted in the power shelf with the
locking screw in both locked and unlocked positions
Insert the rectifier
by
sliding it fully into the power shelf, so that it makes proper contact.
Support from underneath
Lock the rectifier
by
using a screwdriver to turn the locking screw ¼ of a turn counter
clockwise to the locked position (
). Then, the rectifier will be
securely locked in the shelf, or ready for transport