19
“Set-Point pH” (Proportional) mode - Pulse
This mode is valid for any proportional / pulse output available.
Proportional mode set the CONTROLLER to operate using a calculated percentage between two set values that
enable or disable the pH pump. To use this mode tap on “Proportional First Point”. Tap on it.
PROPORTIONAL mode between 7pH(0 P/m) and 8pH (180 P/m). p/m is : pulses per minute
In this mode the pH pump will be “ON” for values greater than 8pH with maximum set pulses per minute capacity (e.g.:
180) and it’ll be “OFF” for values lower than 7pH. For values of 7.5pH pump will be “ON” with 90 pulses per minute
capacity.
7 0
8 180