“Set-Point ppm” (on/off) mode example n.1 tracer
This mode is valid for any “Digital” output available. On/Off mode set the controller to operate using two set
values that enable or disable the TRACER pump. To use this mode tap on “Working Mode”.
ON/OFF mode example 1
Set ppm value at 7.00 OFF and 6.90 ON. Set Pulse Speed per minute (strokes per minute) based on dosing device
capabilities. Controller will leave the tracer pump active until reading value will increase up to 7.00ppm.
At 7.00ppm the tracer pump will be disabled until reading value will decrease under 6.90ppm.
“Set-Point ppm” (on/off) example n.2 tracer
This mode is valid for any “Digital” output available. ON/OFF mode
Set ppm value at 7.00 OFF and 7.10 ON. Set Pulse Speed per minute (strokes per minute) based on dosing device
capabilities. Controller will leave the tracer pump active until reading value will decrease up to 7.00ppm.
At 7.00ppm the tracer pump will be disabled until reading value will increase up to 7.10ppm.
6.90 7.00
ON
OFF
7.00 7.10
ON
OFF