Chapter 5 Operating SCU 51
ACTURA Flex 48330 Power System User Manual
PLC
SN
Alarm
description
Remark
41 Short Test Error
42 BattTest Error
43 LLVD
44 BLVD
45 Outvolt Error
46 Power Failure
47 Multi-Rect Fails Disabled for China Market, Enabled for rest of world
48 Rect Fan Fails
49 Rect Com Failure
50 Rect Vac Err
51 Rect Over Temp
52 Rect Failure
53 Rect Protect
54 Rect Fan Fails
55 Rect PowerLimit
56 Derateby Temp
5.6 Maintenance
Note
1. This operation can be conducted only when the battery management is set to “Manual”.
2. Be careful! BLVD operations may result in power interruption.
Operation Procedures:
1. At any information page, press “ENT” to enter the main menu.
2. Press “
” to select the “Maintenance” menu.
You cannot enter the system Maintenance menu if the “Battery Management” is set
to “Auto”.
3. Press “ENT” and input the correct operation password. Press “ENT” again to
enter the “Maintenance” menu.
Enter Password:
123456